Precision Flow Test Kit - Model 805
Functions and Applications
- Connect hoses to test connections – red high pressure hose upstream, green low
pressure hose downstream.
- Open balance valve (bottom of panel)
- Pull free end of clear plastic tubing from kit.
- Open high and low bleed valves alternately to purge air from system. Bleed water
discharges from convenient clear plastic flexible tubing.
- When bleeding shows all air removed – close bleed valves, balance valve and read
differential pressure.
- When test is complete – open balance valve before disconnecting hoses from test
connections.
- Hoses are stored by coiling them around the test gauge panel.
- Place clear plastic tubing inside case before closing lid.
For convenience in handling, the cover of the test kit is removable. Depress the
pin spring of the top hinge, pull the hinge slightly apart and slide the cover
off. To reinstall, reverse this procedure.
NOTE: The 805 Test Kit is equipped with in line filters near the ends of the
hoses. If the gauges respond slowly to changes in the differential pressure the
filter elements may be partially plugged.
To remedy this, unscrew the two halves of the filter housing and remove brass
filter element. It may be cleaned by flushing with mild detergent and water. If,
after reassembly this has not satisfactorily improved the response time a
replacement filter element kit #98008 should be installed.
MODEL 805 Test Kit Schematic Diagram
